J3676SpH/ORP Control
Systems |
|
SYSTEM LOGIC
The Model is the ideal system for Monitoring, and
Control of pH /ORP. It offers great versatility and finds applications
in effluent monitoring of wastewater, process control, pH neutralization
etc. Fully enclosed in a weatherproof enclosure it is suitable for
outdoor use or in corrosive environments.
The control logic is simple. From the face panel
of the instrument, dial in your set points within which you wish to
control the pH/ORP. |
 |
Plug in your chemical feed pumps into the
receptacles provided on the bottom of the enclosure. When the pH value
rises above the high set point it will activate the acid pump, and lower
the pH until it reaches the set point. If the pH falls below the lower
set point, the base pump is activated until the pH rises to the set
point level and then shuts off In this manner, the pH is always
maintained within your defined pH levels.
ENCLOSURE |
NEW !
Dual PH/ORP
all
contained
in
one NEMA 4X wall mount enclosure
 |
NEMA 4X wall mount enclosure design allows easy
mounting. Impact and chemically resistant construction. Transparent
front door fastened with a hinged latch and provides a clear view of
controller with easy access to front panel adjustments.
Bottom access to plug-in receptacles for pumps and BNC electrode
connectors provide ease of operation. Operating temperature: -10 to 400
C.
|
SPECIFICATIONS:
pH
mV
Range:
0 to 14.00 pH + 1999mV
Resolution:
0.01
pH
1. Om V
Accuracy: (+1
digit) + 0.01
pH
+ 0.1%
Controller Range:
Relay
Output:
0 to 14.00 pH +
1999mV
Current
Output:
0 to 14.00 pH 0 to
1400 mV
Temp
Compensation:
Auto, 0 to 100°C
Temp.
Sensor:
PT -100
Display:
12.7mm high, LED
Power:
115 V AC, 1 Phase |
PROBES
Combination electrode for use in process and waste
applications. Built for Submersion and Inline applications. The outer
body is Ryton and has a 3/4 inch MNPT thread at both ends. An Industrial
Plunger style glass electrode is surrounded by a peripheral Porous
Teflon liguid junction. This design allows the user to mount the
electrode at any angle rather than just vertical as is normal. Comes
standard with a 15ft cable and BNC connector. A high temperature version is available for
greater than 800C (176F)
 |
New Flat Tip pH Probe
No Glass Breakage - Longer Life, Designed for viscous and
heavy
suspended solids
|
|
|

PDS-360 Ultrasonic Open-Channel
Flowmeter
|
Featuring
* 6 Months of Daily Flow
Totals
with Logged Flow Summary
* Time Stamped Data Logging
of Average Flow with Event List
* 5 Programmable Relays
* Two 4-20 mA Outputs
* Quick, Easy Setup
* High "Accuracy
* Non-Contacting
Control
Electronics advanced PDS-360 Ultrasonic Open-Channel
Flowmeter is a highly accurate, noncontacting liquid flow
measuring device. The system is microprocessor controlled
and will monitor flows through any flume or weir.
Applications range from monitoring flow rates in sewage
works to monitoring industrial waste discharge |
|
 |
CONTROLLER
Reliable, Accurate, Smart
Precise flow
depth measurements are continuously made under processor control.
Ultrasonic sound pulses are transmitted from the sensor and elapsed
time of echo return is accurately calculated. This information is
converted to a depth-of-flow and is applied to the respective
equation for the flow device selected. The built-in equations
produce a flow rate and totalized flow.
Proportional analog flow rate
signals, relay contact closures and RS-232/485 outputs are available
for remote indicating, recording, sampling and Downloading of Flow
Data to PC/lapTop.
Complete solid-state design
ensures repeatable, long term, trouble-free operation. All circuits
are protected in a NEMA 4X enclosure with a clear polycarbonate
hinged cover for easy viewing of flow indications. The controller
can be located up to 1500 feet from the measuring site for your
convenience.
|
|
CPS-460 Ultrasonic
Doppler Flowmeter |
|
Featuring
* Detailed Data Logging of Pump
Cycles
* 31 Day Data Logged Flow Summary
* Exclusive Valve Control Algorithm
* NIST Traceable
* High Accuracy
* Non-Invasive
Control Electronics model
CPS-460 Ultrasonic Doppler Flowmeter is a highly accurate,
noncontacting liquid flow measuring device. The system is
microprocessor controlled and will monitor flows of
solid-bearing and/or aerated liquids in most standard pipe
materials. Applications range from monitoring flow rates in
sewage works and industrial waste discharges to controlling
valve positioning and pump rates. |
|

|
|
CONTROLLER
Reliable, Accurate, Smart
Precise
Flow measurements are continuously made by an ultrasonic sound
wave that penetrates through the pipe wall into the flow stream.
Advanced techniques, under processor control, evaluate the
returned Doppler signal, eliminating and rejecting unwanted
components that may interfere with extraction of the true flow
signal. This information is converted to an average flow
velocity and is applied to the respective pipe size ID selected.
The built-in equations calculate a volume flow rate and total
flow. proportional analog flow rate signals, four relay contact
closures, RS-232 and modem(opt) outputs are available for remote
indicating, recording, sampling, valve control and process
control. A detailed Data Logging is also included. All circuits
are protected in a NEMA 4X, IP65 enclosure with a clear
polycarbonate hinged cover for easy viewing of flow indications.
The optional 460R Controller can be located up to 1000 feet from
the measuring site.
|
 |
|
|
METAL IMMERSION HEATERS
* .5 to 54 kW, 35 watts/square inch (5.4 watts/square centimeter) nominal (other sizes and watt densities available). 120, 240, 480 volts standard, 208, 380, 415 and other voltages available.
* Choice of steel, stainless steel (304 and 316) and titanium sheath materials.
* For plating tanks, rinse tanks and other aqueous solutions. Low watt density models available for phosphatizing and concentrated aqueous solutions.
* Single phase standard, three phase available as an option |
 |
| |
FLUOROPOLYMER (PTFE)
HEATERS 10 Watts Per
Square Inch |
|
 |
 |
 |
|
|
Liquid Level Controls
|
Product Features and Benefits:
* Remote probe assembly with 10 foot (3 meter) flexible lead. Quick connect plug for easy connection to remote mounted circuitry.
* Longer, flexible cord on probes available.
* Stainless steel, titanium, Hastelloy CÒ or graphite probes covered with fluoropolymer resin.
* NEMA 4X equivalent, flame retardant plastic case.
* Field selectable 120/208-240 VAC, 50/60 Hz, 5 watts.
* 10 amp, 240 VAC spdt switch capacity.
* 70,000 ohm maximum solution resistance.
* Longer probe lengths available.
* Operating ambient temperature 0 degrees to 120 degrees Fahrenheit.
* Conductivity style devices operate in most electrically conductive solutions by passing a small AC current between probes.
* Two probe units for single level control.
* Multiple probe units for two point control and refill/pump down capabilities.
* Ideal for plating systems, waste treatment tanks and leak detection.
* Capacitive style available for non contact level control. Mount outside of non metallic tanks with thicknesses up to .984 |
| Temperature Controls
DIGITAL CONTROLS |
|
|

|
* 0 degrees to 500 degrees Fahrenheit
temperature range standard (field selectable 0 degrees to 260 degrees
Celsius).
* Auto-tune PID, PID or On-Off control.
* Provides greater accuracy, safety and energy savings.
* Digital indication of process and set point temperature.
* Large switching capacity available.
* Multiple set points for heat/cool applications available.
* High/Low temperature set points for alarms.
|
|
|
|